Technical Specification of Diesel Genset comprising of following components
1.DIESEL ENGINE
2.ALTERNATOR
Synchronous alternator of KIRLOSKAR / CROMPTON / STAMFORD / LEROYSOMER make rated @ 1500 RPM at 0.8 lagging PF at 415 V suitable for 50 Hz 3 phase system. The alternator shall be in SPDP enclosure, IP 23, Class H Insulation, Self excited, Self regulated, Brushless (From 75 kVA) foot mounted with single bearing design. The alternator shall confirm to IS 4722, BS 5000 and IEC 34 and shall be suitable for tropical conditions.
3.ALTERNATOR CONTROL PANEL
Floor mounting type, totally enclosed, vermin proof, louvered steel fabricated SWG 14 Control panel suitable for the above Generator comprising of
4.BATTERIES & BATTERY LEADS
Battery of rated A/H Capacity of STANDARD / EXIDE make to cater the electrical starting of the genset along with the battery leads.
5.FUEL TANK
8 Hours Capacity, Floor mounting type made from 14 SWG MS sheet, duly painted and fitted with inlet outlet , returns connection , air vent , drain value , Gate value , Over flow , Level guage , level indicator and Breather.
6.ARRANGEMENTS
The above Engine and alternator would be Directly coupled. Both the units including the radiator / heat exchanger mounted on a rigid fabricated base frame would be of MS STEEL suitably machined to ensure perfect alignment of the engine and alternator with rigid construction to ensure minimum vibration. The base frame would be provided with lifting facilities and pre-drilled foundation holes suitable for permanent installation on pre-prepared concrete foundation.